How to measure the polarity of the current transformer using the DC method?

The method of checking the polarity of a current transformer using the direct current (DC) method is a simple and effective technique. Here's how it works: First, connect the positive terminal of a battery to the L1 terminal on the primary side of the current transformer. Then, connect the negative terminal of the battery to the L2 terminal. This creates a DC current flow through the primary winding. Next, take a multimeter set to the milliamp or microamp range and connect its positive lead to the K1 terminal on the secondary side of the current transformer. Connect the negative lead of the multimeter to the K2 terminal. Make sure the multimeter is properly configured for the measurement. Now, when you close the switch or turn on the battery, the multimeter needle should move in the positive direction from zero. This indicates that the polarity is correct. When you open the switch or disconnect the battery, the needle should swing in the opposite direction. This reverse deflection confirms that the current transformer is functioning correctly and that the polarity markings are accurate. This method is widely used in electrical testing because it provides a quick and reliable way to verify the polarity of current transformers without requiring complex equipment. It’s especially useful during installation or maintenance work where ensuring correct polarity is critical for safe and accurate operation. Always make sure all connections are secure and that the multimeter is properly set before performing the test.